Insulation:
Resin cicloalifatica with quartz silanizado.
Use:
OUTDOOR
OTHER CHARACTERISTICS:
Measuring block consisting of three current transformers MJE-35 and three voltage transformers MV35-E.
CURRENT TRANSFORMERS
-Normal ratio: 5-10/5 up to 400-800/5 A
-Normal capability: 15VA- class 0.5s- n<=5- ith=80ln.
VOLTAGE TRANSFORMERS
-Normal ratio: 33/V3 / 0.11/V3 Kv.
-Normal capability: 30VA- clase 0.5
NOTE: If you have any doubts, the excurate class could be:
Class: 0.2s for current transformers.
0.2 for voltage transformers.
-For other values of primary current, as well as secondary uses, we suggest you contact our technical service dept